actively carry out the law on civil air defense education, drawn out of the air defense in Pingliang city Building under easy fare, daily special inspection and regulation, overfulfilled the province upper and lower knots of up to 500,000 yuan fee collection tasks. 5, further standardize internal management, improve staff quality. Adhere to the
自动重合闸漏电保护开关在合闸前对线路电压进行检测,当供电电压异常过压、过压情况时,将封锁合闸并报警;故障未经排除,则无法合闸通电。当故障排除时,开关将自动合闸通电。
7.自动重合闸特性:(可调试)
线路发生瞬间漏电或瞬间冲击(如雷电、插座跳火等)而可能有危险时,BJ自动重合闸漏电保护开关立即断开;故障过后,线路如是安全,自动重合闸漏电保护开关会自动重新合闸通电。合闸次数为无限次,前3次数合闸时间分别为1、2、3分钟,后5次合闸时间均为5分钟,过后合闸时间为30分钟+N次。
8.电压与跳闸次数显示:
CHET系列的自动重合闸漏电保护开关带有显示屏显示功能,能准确地显示现场电压,电流,漏电流,跳闸次数等实时现场数值,并且能通过“显示切换”按键,分别显示各项参数;第四个显示管如果是“U”,表示当前显示的是现场电压,单位是伏;如果是“a”,表示当前显示的是现场电流,单位是安培;如果是“L”,表示当前显示的是现场漏电流,单位是毫安培;如果是“n”,表示当前显示的是跳闸次数。
9.手动通断性能:
9.1、手动按下试验按键漏电时,零线与火线应同时断开,无输出。30秒自动合闸,自动重合闸开关状态正常。
9.2、手动关闭电源开关后,两路继电器同时断开,无输出。。重新起动开关电源,两路同时输出,自动重合闸状态正常。
10.电气强度:施加1500V、50Hz、5mA、1S下列部位,无闪络击穿现象。
11.防雷试验:
CHET系列开关能承受GB/T17626。5-1999中试验等级为4极,电源线L-N间流过8/20us,10KA的雷击浪涌电流,样品不损坏。
 四、安装:
(1)将本开关安装于主机箱内,避免直接雨淋、日晒。
(2)装保护器接在断路器或闸刀开关的下方,电源输入端,负载接输出端。
(3)如果