监理规划
批准:
审核:
编制:
河南立新电力建设监理有限公司
2008年09月01日
目录
···············································3
·················································9
·················································10
·················································15
·················································17
·································18
7. 项目监理机构的人员配备计划·································19
8. 项目监理机构人员岗位职责····································
21
···············································23
10. 监理工作方法及措施·········································24
11. 监理工作制度···············································63
12. 本项目中使用的主要仪器设备一览表···························64
13. 附表·······················································65
:国电驻马店热电厂扩建工程。
:厂址位于距离驻马店市区东北约3km(现有市区边缘)的遂平县石寨铺乡刁庄村附近。,东距刁庄村约300m,南距坡王庄约350m,北距文集村约400m。场地东、西侧分别为市区规划道路驿城大道和前进大道。
:本工程建设规模为2×300MW燃煤供热机组。
:本工程项目计划总资金:266609万元,由中国国电集团公司和驻马店市投资有限公司合资建设经营。
:本项目可行性研究报告通过了电力规划设计总院主持评审,其他各项专业评审工作已基本完成。经河南省发展改革委员会和中国国电集团公司上报到国家发展和改革委员会,国家发展和改革委员会已下发了同意本工程开展前期工作的文件。项目设计招投标工作已经完成,厂区围墙施工正拟实施。
(项目法人):国电驻马店热电有限公司。
本期工程拟定于2008年8月开工,第一台机组于2009年12月投产,第二台机组于2010年3月投产。
锅炉:亚临界参数燃煤汽包锅炉,单炉膛,一次中间再热、平衡通风、固态排渣、露天布置、全钢架悬吊结构。
汽轮机:亚临界、单轴、三缸双排汽、一次中间再热、抽凝供热式。
发电机:发电机的冷却方式为水-氢–氢,自并励静止励磁系统。
主蒸汽系统、再热热段蒸气系统均采用1-1-2制。
每台机组按设置一套容量为40%锅炉最大连续出力的二级串联旁路系统。
汽轮机具有八级非调整抽汽,分别作为3台高加、1台除氧器和4台低加的加热汽源。四段及五段抽汽供除氧器及
5号低加,四段抽汽同时向高压厂用辅助蒸汽联箱供汽。
给水系统为单元制,每台机组设置2台50%容量的汽动给水泵和1台30%容量的启动电动给水泵。每台主泵均配有一台前置泵。
凝结水由凝汽器热井经总管引出,然后分3路至3台55%容量的凝结水泵(二台运行,一台备用),合并成一路后经中压凝结水精处理设备、汽封加热器、低压加热器至除氧器。
加热器疏水采用逐级回流。正常运行时,高加疏水逐级回流至除氧器,低加疏水逐级回流最终至凝汽器。
两主机可调抽汽分别经快关止回阀和摇板止回阀后,引至供热首站。首站设四台热网加热器、四台热水调速循环泵和四台疏水泵,疏水打入除氧器。
制粉系统:拟采用双进双出钢球式磨煤机系统。
每台锅炉配2台动叶可调轴流一次风机,2台动叶可调轴流式送风机,2台静叶可调轴流式引风机。
本工程选用除尘效率≥%的布袋除尘器,每台锅炉配用1台布袋除尘器。两台锅炉合用一座外钢筋混凝土内钢单套筒烟囱。
本工程同步建设烟气脱硫系统,
国电驻马店监理规划 来自淘豆网m.daumloan.com转载请标明出处.