消防风机_消防水泵联动接口方案探讨消防风机、 消防水泵联动接口方案探讨*
李慧 徐建兵 郑宇(中国建筑西南设计研究院有限公司, 成都市 610042)
Discussion on Interface Solution for Firefighting Fan, Fire Pump Automatic Control System*
LI Hui XU Jianbing ZHENG Yu (China Southwest Architectural Design and Research Institute CORP. Ltd., Chengdu 610042, China)
Abstract: According to automatic control, manual control and signal feedback requirements of firefighting equipment, a solution of setting an on-site device box as the interface between automatic control system and electrical control is proposed, thereby taking into account different system forms and capacities of the firefighting products of any brand. Besides, the interfaces of firefighting fan, fire pump control circuit and automatic control system are demonstrated, and issues of the interface solution’s differences of national standard atlas are presented.
Key words: firefighting equipment; automatic control system; manual direct control; automatic control; on-site device box; firefighting interface; control circuit; CPS
摘要: 为兼顾各种品牌消防产品在系统形式、容量等方面的不同, 根据消防设备自动控制、手动控制及返回信号要求, 提出设置现场器件箱作为连接消防联动控制系统和电气控制箱接口的解决方案。同时, 给出消防风机、消防水泵控制电路与消防联动控制系统接口示例, 并对与国标图集的差异进行了阐述。
关键词: 消防设备; 消防联动控制系统; 手动直
接控制; 自动控制; 现场器件箱; 消防接口; 控制电路; CPS
中图分类号: TU892 文献标识码: A
0 引言
在建筑电气施工图设计中, 对有控制要求的回路应提供控制原理图, 国标图集 10D303 - 2 ~ 3 《常用电机控制电路图》给出了常用电机的控制原理图, 给广大设计人员提供了极大的便利。为了让消防风机、消防水泵控制电路图中, 联动控制与现行设计规范、产品标准结合得更加紧密, 笔者在完成中建西南院科研