一起辅助变压器跳闸事故分析
(中核集团三门核电有限公司调试处浙江 317112)
摘要: 220kV电源作为核电厂的辅助电源,对于核电厂的安全运行至关重要。本文通过一起核电厂的辅助变跳闸事故,寻找跳闸原因,做好防范措施,杜绝类似事故发生,为核电厂的安全运行积累经验。
关键词:辅助变压器、差动保护、跳闸
analyses of the auxiliary transformer protection trip
LIANG Lin
(Sanmen Nuclear pany, Ltd., Zhejiang 317112, China)
Abstract: The 220kV auxiliary power source system is important to safety operation of the nuclear power plant. The 220 kV transformer is an important element in this auxiliary power system. This paper introduces an auxiliary transformer protective trip in one nuclear power plant, and finds out the reason of the trip to avoid the same occasion and accumulate the experience of the safety operation of the nuclear power plant.
Key words: the auxiliary transformer; the transformer differential protection; trip
1 引言
某核电厂220kV电源是机组的辅助电源,是保障安全的第二路厂外电源系统,在机组正常启动和停机过程中作为优先电源500kV电源的后备电源。当失去优先电源时,厂用负荷切换到辅助电源(220kV电源)。另外,在机组正常运行时,如中压母线失去厂用进线电源,则由辅助电源(220kV电源)通过辅助变压器向厂用负荷供电。并且在核电厂建设期间,该电源作为下游系统调试开始的前提条件。由此可见,辅助电源系统对于核电厂的安全运行来讲至关重要,其相
关的跳闸故障需要深入分析,并做好经验反馈。
该核电厂220kV系统采用双母线接线方式,配备室内气体绝缘金属封闭开关(GIS)设备,由 220kV电缆连接辅助变压器与GIS设备。辅助变压器下游配置有10kV中压进线断路器和辅助锅炉断路器。具体设备运行方式详见图1。
辅助变压器配置的保护有:差动、辅助变高压侧速断过流、辅助变高压侧反时限过流、高压侧过负荷、低压侧过负荷、辅助变低压分支零差保护、辅助变过激磁。中压保护的配置情况为:中压母线进线断路器配置了过流一段保护、过负荷保护和接地一段保护。辅助锅炉断路器保护配置了过流一段保护、过负荷保护和接地一段保护;进线断路器的过流保护启动值和时间均与馈线断路器相应保护定值配合,从而保证保护的选择性。
2 事故处理
某日在进行辅助锅炉启动试验中,两套辅助变保护的差动保护ABC三动作跳闸出口。辅助变差动保
一起辅助变压器跳闸事故分析 来自淘豆网m.daumloan.com转载请标明出处.