500kV 线路 IVI 型双回路直线铁塔的规划设计
余朝胜
(福建省电力勘测设计院福建福州 350003)
Design of IVI type Double-circuit Suspension Tower
for 500kV transmission line
YU Chao-sheng
(Fujian Electric Power Survey and Design Institue,Fuzhou 350003,China)
Abstract : For scientific planning IVI type 路为同塔双回线路长度 115km,导线采用 4×
double-circuit Suspension tower for 500kV ACSS-400/50 节能型软铝导线,一根地线采
transmission line , based on mathematical expectation 用 JLB40-150 铝包钢绞线,另一根地线采用
of optimization theory analysis, this paper decorate a OPGW 光缆。气象重现期按 50 年一遇,离地
line-hanging method, economic span planing etc., 面 10m 高,基准风速取 ,导线覆冰
and obtains the optimal design, it proves that the new 按 10mm 考虑,地线覆冰按 15mm 设计,海拔
layout program has greater advantages based on 在 150-600m,地形为:山地占 %,平丘
economic and technical analyses,so IVI has a broad 占 %。
application value. 2 杆塔挂线布置型式选择
Key words: transmission line; double-circuit; 影响一个工程的技术指标主要在于直
suspension tower ;design 线塔。本工程的直线塔约 227 基,转角塔约
25 基,直线塔的挂线布置型式直接决定了整
摘要:为科学规划 500kVIVI 型双回路直线塔,该文个工程的造价。双回路直线塔的导线排列方
从挂线布置形式、经济档距规划等方面,采用基于式主要分为垂直排列和三角排列两种。国内
数学期望的最优化理论进行最优设计,最终得出该的同塔双回路铁塔,除大跨越塔为了减少塔
塔型在技术和经济有较大的优势,具有广泛的应用高,采用三角排列外,一般线路多采用三相
价值。导线垂直排列的方式。垂直排列由于线路走
关键词: 线路双回路直线塔设计廊较小、回路明确、结构简单、传力清晰、
施工和检修较为方便,在国内大量使用,同
根据 500kV 双回线路建设情况,铁塔一时积累了丰富的运行经验。因此本工程推荐
般占本体投资的 35%左右,杆塔规划及经济采用垂直排列塔型。
档距的合理确定,对降低工程投资起关键作以山地 II 型直线塔为例,根据不同绝
用。本文就黑龙江庆云变至鸡西变 500k
500kV线路IVI型双回路直线铁塔的规划设计 来自淘豆网m.daumloan.com转载请标明出处.